VAULT

Private · Master Plan · v1.0
VAULTHVAC CLEANING

VAULT HVAC AND CLEANING

Owner: Director of Facilities, GM approval on any spec change Standard: pandemic-grade air handling, hospital-grade sanitation, luxury-grade finish. Members should never see a cart, a mop bucket, or a chemical smell.


1. AIR HANDLING DESIGN INTENT

VAULT’s HVAC is designed to accomplish four things at once:

  1. Remove airborne pathogens, allergens, and combustion byproducts.
  2. Hold precise temperature and humidity per zone.
  3. Deliver ventilation rates that keep CO2 low and cognitive performance high.
  4. Do all of the above at whisper-quiet operation, under NC 30 in guest zones and under NC 35 on the training floor.

1.1 Zone setpoints

Zone Temperature Relative humidity CO2 target NC target
Lobby 70 F 40 to 50 percent under 800 ppm NC 30
Members lounge 70 F 40 to 50 percent under 800 ppm NC 30
Cafe 70 F 40 to 50 percent under 800 ppm NC 35
Main training floor 68 F 40 to 50 percent under 900 ppm NC 35
Pole studios 74 to 76 F 40 to 50 percent under 900 ppm NC 35
Private pole and dance rooms 74 to 76 F 40 to 50 percent under 900 ppm NC 30
Recovery deck 72 F 45 to 55 percent under 800 ppm NC 25
Locker rooms 72 F 45 to 55 percent under 900 ppm NC 30
Sauna room ambient (outside cabin) 72 F 40 to 50 percent under 900 ppm NC 30

Humidity in pole studios is held toward the top of the range for grip. Recovery deck humidity is held higher for skin comfort post-plunge.

1.2 Filtration and treatment

  • MERV 14 pleated filters at the return of every air handler, replaced on a 60 day cadence or on differential pressure alarm, whichever comes first. Preferred spec: AAF Flanders VariCel or Camfil Hi-Flo XLT MERV 14 in matching frames.
  • UV-C germicidal lamps installed in every air handler downstream of the coil, sized to deliver a validated kill dose against common respiratory pathogens at design airflow. Bulbs replaced annually or per manufacturer’s lumen depreciation curve. Lamps interlocked to service switches so they cannot be viewed by a technician while energized.
  • Bipolar ionization or needlepoint ionization at the supply plenum where the design supports it, targeting neutralization of surface and airborne particulates. System selected must have UL 2998 zero ozone emission certification. No exceptions.
  • HEPA units as standalone in the recovery deck locker vestibule and in the medical screening room off the main floor.

1.3 Ventilation rates

  • Air changes per hour (ACH) target: minimum 6 ACH total in every guest occupied zone, with minimum 3 ACH of outside air where the building envelope and load permit.
  • Training studios operate at 8 ACH total during class and step up to 12 ACH for 6 minutes at end of class as the exhaust purge cycle.
  • Sauna and steam room mechanical exhaust runs continuously at design rate. Ambient sauna room exhaust ramps up during peak.
  • Cold plunge deck exhaust sized for latent load control, humidity held below 55 percent to prevent musty odor and biofilm growth on ceilings.

1.4 Humidity strategy

  • Central humidification via steam injection for winter operation. Steam quality tested annually.
  • Central dehumidification integrated with cooling coils and reheat, or dedicated outdoor air system (DOAS) with wheel, per the mechanical design.
  • Pole studios have local sensors calibrated quarterly. Reading logged at open, midday, and close. If humidity falls below 35 percent or climbs above 55 percent, members are notified politely and grip aids are offered gratis while the system corrects.

1.5 Commissioning and verification

  • Full commissioning at opening by an independent commissioning agent, sealed report on file.
  • Recommissioning every 3 years.
  • Airflow at every diffuser measured with hood annually.
  • Filter differential pressure logged weekly.
  • CO2 monitored continuously in every zone, logged to the ops system, alarm on threshold.
  • UV-C lamp intensity measured annually with a UV meter.
  • Duct interior inspected every 3 years by camera, cleaned per NADCA standard on any finding.

2. WATER SYSTEMS

2.1 Domestic hot water

  • Delivered at fixtures at 104 to 108 F for showers, 110 F at sinks with anti-scald mixers.
  • Recirculation loop maintains temperature to reduce Legionella risk. Legionella testing quarterly, cultured by an accredited lab.
  • Point of use booster where needed for the cafe and laundry.

2.2 Cold plunge

  • Filtration: 10 to 20 micron mechanical pre-filter, UV plus ozone treatment, secondary sanitizer (chlorine or bromine per unit spec).
  • Chemistry logged 4 times daily: open, midday, evening peak, close.
  • Targets: free chlorine 1.0 to 3.0 ppm, pH 7.2 to 7.6, ORP above 650 mV, total alkalinity 80 to 120 ppm, calcium hardness per unit spec.
  • Skimmer emptied at every log entry.
  • Weekly deep sanitation cycle out of hours: drain 25 percent, refill, shock treat, run filtration overnight, retest before open.
  • Quarterly full drain, chamber sanitation, refill.
  • Water quality testing sent to an accredited lab monthly.

2.3 Steam room

  • Steam generator descaled per manufacturer, quarterly minimum.
  • Aromatherapy injection uses medical grade oils only, from the approved spa oil vendor on 04_VENDOR_ROSTER.md. No member-supplied oils.

3. CLEANING PRODUCT SPECIFICATION

VAULT uses professional grade, EPA registered chemistry. Products are staged in staff-only cabinets, never in view of members, never in aerosol form on the training floor.

3.1 Approved product SKUs

  • Multi-surface disinfectant. Diversey Oxivir Tb (accelerated hydrogen peroxide), or Ecolab Peroxide Multi Surface Cleaner and Disinfectant. EPA registered, effective against enveloped viruses and common respiratory pathogens, 1 minute contact time, low residue, no VOC odor.
  • Bathroom cleaner and descaler. Ecolab Neutral Disinfectant Cleaner for daily wipe downs, Ecolab Bowl Cleaner for toilets, Ecolab Descaler Delimer for weekly showerhead and fixture treatment.
  • Floor cleaner, resilient and hard surface. Diversey Stride Neutral Cleaner for daily damp mop. Betco Fastdraw for weekly scrub on training floor and locker rooms.
  • Wood floor cleaner, dance studios. Bona SuperCourt Cleaner. Diluted per spec, applied with microfiber flat mop only.
  • Pole grip-safe cleaner. Isopropyl alcohol 70 percent, applied with lint-free microfiber. No detergents. No residue.
  • Aerial silk cleaning. Front-load washer, warm cycle, mild non-optical-brightener detergent (Ecos Pro or equivalent), no fabric softener, no dryer sheets. Air dried, never machine dried.
  • Mat sanitation. Diversey Oxivir Tb applied via electrostatic sprayer between classes. Manual wipe on any visible soil.
  • Sauna wood care. Manufacturer-approved wood cleaner for benches and walls. Never bleach, never quats on interior sauna wood.
  • Steam room. EPA registered quaternary disinfectant rated for steam room use, applied with dedicated mop and cloth.
  • Cold plunge deck. Diversey Oxivir Tb on non-slip surfaces. Enzymatic drain cleaner weekly to prevent biofilm.
  • Glass and mirror. Ecolab Facilipro Glass Cleaner. Microfiber only.
  • Stainless. Ecolab Facilipro Stainless Steel Cleaner Polish. No aerosol.

Product changes require Director of Facilities approval and updated safety data sheets in the ops system.

3.2 Application standards

  • Color coded microfiber system: blue for glass and mirror, yellow for general surfaces, red for restrooms, green for cafe. Never crossed.
  • Microfiber laundered daily by internal or contracted laundry per 04_VENDOR_ROSTER.md. Never reused between zones without laundering.
  • Electrostatic sprayer used for between class turnovers on mats and floors. Handheld sprayer used in private studios.
  • Contact time observed. Members are never rushed through a wet surface.
  • No aerosol cans on the floor in guest hours.

4. CLEANING CADENCE BY ZONE

4.1 Lobby and members lounge

  • Continuous touch-point wiping during operating hours. Door handles, host stand, seating armrests every 30 minutes.
  • Full floor mop twice daily, mid-morning and evening close.
  • Furniture polish weekly.
  • Deep clean overnight monthly: furniture pulled, baseboards wiped, upholstery inspected, spot cleaned.

4.2 Cafe

  • Kitchen deep clean nightly per food safety plan.
  • Espresso machine backflush and group head clean nightly. Full descale weekly.
  • Refrigeration coils cleaned monthly, gaskets sanitized weekly.
  • Coffee bar wiped every 15 minutes during service.

4.3 Main training floor and pole studios

  • Between-class turnover per 01_DAILY_RITUALS.md Section 4.
  • Full floor mop after each peak block, 3 times daily.
  • Weekly deep scrub with autoscrubber on the main floor.
  • Monthly overnight refinish assessment for wood dance floors.
  • Poles wiped between users, deep cleaned with 70 percent isopropyl and lint-free microfiber every close.
  • Aerial silks laundered per Section 3.1 after every use above beginner. Beginner classes use dedicated silks laundered weekly.
  • Mirrors wiped every close.

4.4 Private pole and dance rooms

  • Turnover between bookings: 30 minutes buffer, full sanitation.
  • Fresh linens if the room has any upholstered element.
  • Music preset reset to house default.

4.5 Locker rooms

  • Continuous attendant presence during operating hours.
  • Surfaces sanitized every 30 minutes on rolling schedule: sinks, counters, door handles, bench tops, locker exteriors.
  • Floors mopped every 45 minutes.
  • Showers wiped between users, walls squeegeed, drain hair pulled, tile spot sanitized.
  • Overnight deep clean nightly: full shower descale, grout treatment weekly, drain enzymatic treatment nightly, tile scrubbed with autoscrubber on tile setting.
  • Amenity restock every 45 minutes and full restock overnight.
  • Robes and towels sent to laundry after every use, no reuse.

4.6 Recovery deck

  • Sauna interior wood benches wiped every 30 minutes with the sauna-safe wood cleaner. Between-session towel change on member towels.
  • Sauna deep clean nightly: benches sanitized, floor sanitized, walls spot checked, heater rocks inspected weekly.
  • Steam room walls, floor, and bench sanitized every 30 minutes with quat disinfectant safe for steam.
  • Steam room drained and dried nightly.
  • Cold plunge skimmed at every chemistry log. Wiped surround every 30 minutes.
  • Contrast shower stations wiped between users, deep cleaned nightly.
  • Eucalyptus towel cooler cleaned and sanitized nightly.

4.7 Restrooms

  • Continuous attendant checks every 20 minutes during operating hours.
  • Full clean every hour minimum.
  • Overnight deep clean.
  • Floral or scent element refreshed on schedule per 04_VENDOR_ROSTER.md.

4.8 Retail micro-boutique

  • Dusted every open. Product straightened continuously.
  • Fitting mirror wiped every 30 minutes.
  • Overnight inventory reconciliation.

4.9 Back of house

  • Staff areas held to the same standard as guest zones. Staff bathrooms, break room, and storage are cleaned overnight and spot cleaned midday.
  • Chemical storage inventory audited weekly. Safety data sheets current.

5. LINEN AND LAUNDRY

  • Robes, hooded towels, bath sheets, hand towels, and washcloths turn once per member visit, no reuse.
  • Practice kit is single use, laundered by the laundry vendor.
  • Aerial silks laundered per Section 3.1 in house on the low-abrasion cycle.
  • Microfiber cleaning cloths sent out daily.
  • Vendor delivers fresh stock at 5:00a and picks up soiled at 10:00p per 04_VENDOR_ROSTER.md.
  • Linen inventory par set at 3 turns: one on the floor, one in transit, one in reserve.

6. PEST AND ODOR MANAGEMENT

  • Integrated pest management program contracted annually. Monthly service visits, treatment plans reviewed by the Director of Facilities.
  • Odor management is a system, not a spray. If a zone smells like anything other than the intended scent, the fix is airflow and cleaning, not fragrance masking.
  • Any staff or member complaint about scent triggers a same-day inspection by the Facilities tech.

7. AUDITS

  • Weekly internal walkthrough by Director of Facilities against this document.
  • Monthly cross audit by Director of Hospitality (fresh eyes).
  • Quarterly mystery member audit by third party.
  • Annual environmental services audit by the cleaning vendor’s field supervisor.
  • Legionella testing quarterly, results filed with GM.
  • HVAC preventive maintenance quarterly by mechanical contractor. Written report with photos.

8. SIGNOFF

Every entry in this document ties to a logged task in the ops system. If it is not logged, it did not happen. Logs are reviewed by the GM weekly and archived for the life of the club.